PROJECT PERFORMANCE
Win with excellence, win the trust with sincerity, provide better and more satisfied products for the new and old customers
Splatter
Whether the cooling effect of the cooling tower is good or not, whether the heat exchange between the water and gas in the filler is sufficient, and whether the efficiency of the filler can be exerted well, the spray device plays an important role.
Material properties of spray device
| Number | Project name | Symbol | Unit | Index | ||
| ABS | PP | |||||
| 1 | Tensile strength (temperature) | Before hot water aging | δt | MPa | ≥40.0 | ≥30.0 |
| After hot water aging | ≥36.0 | ≥30.0 | ||||
| 2 | Izod notched impact strength | Before hot water aging | ak | 10-2KT/m | ≥10.0 | ≥4.0 |
| After hot water aging | ≥4.0 | ≥4.0 | ||||
| 3 | Vicat softening temperature | - | Tv | ℃ | ≥90 | ≥150 |
Specifications and technical performance of various splash devices
| Number | Model | Nozzle size | Flow Coefficient | Applicable conditions | Scope of application | |||
| Working head | Layout size | Splash height | ||||||
| 1 | RC type | Φ21-26 | 0.92 | ≥0.7m | 1m×1m | 0.5~0.8m | Power, natural ventilation tower | |
| 2 | TR-2 type | Φ25-32 | 0.92 | ≥0.7m | 1m×1m | 0.5~0.8m | Power, natural ventilation tower | |
| 3 | XP type | XPH type | Φ32-50 | 0.43 | ≥0.5m |
1m×1m 1m×1.25m 1.25m×1.25m 0.8m×0.8m 1.0m×1.0m |
0.6~1.9m |
Power, natural ventilation tower Pipe trough water distribution |
| XPZ type | Φ28-42 | |||||||
| 4 | Reflective | II type | Φ25-42 | 0.92 | 0.3-0.4m | 1m×1m | 0.8m |
Power, natural ventilation tower Tower trough water distribution |
| III type | Φ25-42 | |||||||
| 5 | Multilayer flow pattern | Φ30-48 | 0.92 | ≥0.4m | 1m×1m | 0.8m | Tube and trough water distribution | |
Spraying equipment various accessories
| Number | Name | Specification | Material | Note |
| 1 | Fixing nut | M6×40×25 | ABS | |
| 2 | Screw | Stainless steel | RC spray | |
| 3 | Nut | M6 | Stainless steel | Head tube |
| 4 | Washer | Φ14×6×1.5 | Stainless steel | For water distribution |
| 5 | Spring washer | Φ6 | Stainless steel | |
| 6 | Extended takeover | Φ40 | ABS | For reflective |
| 7 | Dedicated connector | Φ40(Φ30) | ABS | For reflection II old tower reconstruction |
| 8 | Pipe hoop | M60×4 | ABS | |
| 9 | Big and small | M48×4/M36×4 | ABS | For reflective sprinklers |
| 10 | Connector | Φ40 | ABS | |
| 11 | Tee joint | Φ75×Φ50 | ABS | |
| 12 | Fastening nut | M64×4 | ||
| 13 | Arm tube | Φ65×7 | ||
| 14 | Reducer | M64×4/M60×4 | For XP nozzle | |
| 15 | Connector | Φ74 | ||
| 16 | Extension tube | Φ74 | ||
| 17 | Pipe hoop | Φ74 | ABS |
Spray device quality standards
1. The appearance of the spray device should be smooth, complete, and consistent in color, and there should be no cracks, holes, depressions or obvious impurities;
2. Each threaded connection should be well-coordinated, moderately tight, and move forward and backward freely.
Installation quality requirements of spray device
1. The nozzles of different calibers shall be in place in the corresponding areas according to the design requirements, and shall not be installed in the wrong place;
2. The installation of the spray device must be firm and reliable. The correct orientation of the spray head and its special joint should be controlled to ensure that it will not fall off, shift or skew in long-term use.
![]() |
![]() |
![]() |
![]() |
![]() |
| RC type spray device | TP-Ⅱ type spray device | XPH Improved spray device | XPH type spray device | XPZ type spray device |
![]() |
![]() |
![]() |
![]() |
![]() |
| Arm tube | Multi-layer flow type spraying device | Reflective Splash Device | Pipe flange, tee | Extension tube |
![]() |
![]() |
![]() |
||
| Elbow | Reducer | Embedded flange, tee |